3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat The free chlorine level is 0 ppm while the pool remained open.
This violation is a critical operational item and poses an imminent health hazard. KEEP MUST CLOSE IMMEDIATELY AND REMAIN CLOSED UNTIL THIS VIOLATION IS CORRECTED AND THE HEALTH DEPARTMENT VERIFIES THE CORRECTION. Correct By: 13-Jul-2020
3701-31-04 (B)(1)(g) / Water clarity shall be sufficient to see the pool bottom (or Secchi disc).
Critical Water clarity was not sufficient to see the pool bottom (or Secchi disc)
Do not operate the pool when water clarity is poor.
This is a critical operational item and poses and imminent health hazard. CLOSE THE POOL IMMEDIATELY AND KEEP POOL CLOSED UNTIL THE VIOLATION HAS BEEN CORRECTED AND THE HEALTH DEPARTMENT VERIFIES THE CORRECTION. Correct By: 13-Jul-2020
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
MAKE RECORDS AVAILABLE TO HEALTH DEPARTMENT DURING INSPECTIONS. Correct By: 15-Jul-2020
3701-31-04 (B)(6)(b) / Replacement pipe is rigid PVC or the equivalent
Repeat Replacement pipe was not rigid PVC or equivalent.
Replace the non rigid PVC pipe with the proper rigid PVC pipe for public swimming pools.
REPLACE RUBBER COUPLINGS. Correct By: 15-Jul-2020
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER OR INCREASE FLOW RATE. Correct By: 15-Jul-2020
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
REPLACE THE MISSING LADDER IN THE DEEP END. Correct By: 15-Jul-2020
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN THE HAND RAIL ON THE STEPS. Correct By: 15-Jul-2020
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Repeat Deck surfaces had standing water or other hazards.
Repair areas of the deck where standing water is occurring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
REPAIR THE UNEVEN DECK. Correct By: 15-Jul-2020
3701-31-04 (B)(6)(r) / Safety line(s) are maintained
Safety line(s) were not maintained in place.
Safety lines must be in place when required to alert the bathers of the change in depth of the pool.
INSTALL A SAFETY LINE WITH INTERMITTENT FLOATS. Correct By: 15-Jul-2020
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The latch on the gate is missing.
REPLACE THE MISSING LATCH ON THE GATE. Correct By: 15-Jul-2020
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH Correct By: 15-Jul-2020
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST THE ALKALINITY. Correct By: 15-Jul-2020
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Repeat Test kit has expired and is not DPD.
OBTAIN A DPD TEST KIT. Correct By: 15-Jul-2020
3701-31-04 (E)(2)(a)(iii) / A back/spine board is provided
A back/spine board without a head immobilizer and straps was not provided at the unguarded pool. Handle is broken.
Provide the back/spine board at the pool at all times.
REPLACE THE SPINE BOARD. Correct By: 15-Jul-2020
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
PROVIDE A FIRST AID KIT AT THE POOL. Correct By: 15-Jul-2020
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
PROVIDE AN EMERGENCY PHONE AT THE POOL WITH EMERGENCY NUMBERS POSTED BY THE PHONE. Correct By: 15-Jul-2020
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
Repeat The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use.
ADD SIGNAGE AS REQUIRED. Correct By: 15-Jul-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 13-July-2020
Comments |
---|
-When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm -Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. -The Certificate of Compliance was not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. -Our records show that the main drain suction outlet cover (Hayward WG1048E) was installed 6/28/2017. The cover has a 7 year life span and must be replaced before 6/28/2024. |