3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation. Flow meter float not moving freely.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR OR REPLACE THE FLOW METER. A SIMPLE CLEANING MAY SOLVE THE PROBLEM. Correct By: 14-Nov-2022
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not tested monthly
Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC FLOW SWITCH FUNCTION MONTHLY. Correct By: 14-Nov-2022
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not properly supplied.
Provide first aid equipment, including a first aid kit, at the pool at all times.
REPLACE MISSING GLOVES IN THE FIRST AID KIT. Correct By: 14-Nov-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 08-November-2022
Comments |
---|
TO HAVE A MARGIN OF SAFETY, IT IS RECOMMENDED THAT THE FREE CHLORINE LEVEL BE MORE THAN 1 PPM. |