3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Records were not available on the main drain covers.
PROVIDE THE CERTIFICATE OF COMPLIANCE FOR THE MAIN DRAIN COVERS AND THE NAME OF INSTALLER WITH THE DATE OF INSTALLATION. KEEP A COPY OF THE RECORD AT THE POOL Correct By: 05-Jul-2019
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON THE FILTER BACKWASH LINE. Correct By: 05-Jul-2019
3701-31-04 (B)(6)(cc)(i) / Starting blocks and diving platforms shall be maintained in good repair.
Starting blocks were in disrepair.
Repair, restore or replace the starting blocks to good repair.
PLACE ALL 4 SCREWS IN THE STARTING BLOCKS AND TIGHTEN. Correct By: 05-Jul-2019
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 316 GPM Correct By: 05-Jul-2019
3701-31-04 (B)(6)(n) / Proper pool operating water level is maintained
The operating water level of the pool was not maintained.
Increase the volume of the pool water until the pool operating water level is restored.
MAINTAIN WATER LEVEL SLIGHTLY ABOVE THE GUTTER. Correct By: 28-Jun-2019
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
REPLACE THE MISSING TREAD OF THE STEPS OF THE LADDER. Correct By: 05-Jul-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate door was propped open.
The gap under the fence and more than 4 inches.
KEEP GATE CLOSED.
INSTALL ADDITIONS TO THE FENCE TO ELIMINATE GAPS IN THE FENCE THAT ARE MORE THAN 4 INCHES. Correct By: 28-Jul-2019
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
ATTACHE THE CHEMICAL PUMPS TO THE WALL OR SHELF SO THEY CAN NOT TIP OVER. Correct By: 05-Jul-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY Correct By: 28-Jun-2019
3701-31-04 (D)(7)(c) / Audible/visual alarm shall activate when unit is malfunctioning or when pH or ORP levels are not acceptable.
Critical The ACC unit was not activating an audible or visual alarm when unit malfunctioned or when pH or ORP levels were not acceptable.
Have the ACC unit serviced or replaced so that the audible or visual alarm is activated when necessary.
REPAIR THE ACC FLOW SWITCH Correct By: 05-Jul-2019
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC FLOW SWITCH FUNCTION MONTHLY Correct By: 05-Jul-2019
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area.
Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area.
POST A SIGN STATING THE LOCATION OF THE EMERGENCY PHONE.
POST A SIGN AT THE PHONE " DIAL 9-911 IN CASE OF AN EMERGENCY" Correct By: 05-Jul-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 27-June-2019
Comments |
---|
Our records show: The main drain suction outlet cover (AquaStar WAV12) was installed 5/1/2008. The cover has a 5 year life span and must be replaced before 5/1/2013. |