3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
TEST AND RECORD THE COMBINE AND TOTAL CHLORINE ON THE WEEKLY LOG SHEET. Correct By: 09-Jun-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The flow meter is not located according to the manufacturers instructions.
All equipment must be maintained in accordance with the manufacturers specifications.
RELOCATE THE FLOW METER PROPERLY. 10 TIMES THE DIAMETER OF THE PIPE DOWN STREAM FROM THE ELBOW IN THE PIPE AND AT LEAST 5 TIME THE DIAMETER OF THE PIPE UP STREAM FROM THE ELBOW IN THE PIPE. Correct By: 15-Jun-2021
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention devices were not maintained to function properly. The backflow preventer is a ASSE 1015. A ASSE 1013 is required.
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
CALL NORTH RIDGEVILLE WATER DEPARTMENT FOR AN INSPECTION OF YOUR BACKFLOW PREVENTER AFTER INSTALLING THE APPROPRIATE ASSE 1013 BACKFLOW PREVENTER. Correct By: 15-Jun-2021
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 76 GPM Correct By: 09-Jun-2021
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
REPAINT HE DEPTH MARKINGS AND NO DIVING MARKINGS ON THE DECK. Correct By: 15-Jun-2021
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FLOW SWITCH FUNCTION AND RECORD ON THE WEEKLY LOG SHEET. Correct By: 09-Jun-2021
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The test kit provided was not in good repair. Reagents expired.
Maintain the test kit in good repair to conduct water quality tests.
REPLACE THE TEST KIT REAGENTS THAT ARE EXPIRED. Correct By: 09-Jun-2021
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use.
POST SIGN "SWIMMING ALONE IS NOT RECOMMENDED" AND "CHILDREN MUST BE SUPERVISED" Correct By: 15-Jun-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 08-June-2021
Comments |
---|
A SCREW IS POSSIBLY MISSING FROM ONE SIDE OF THE MAIN DRAIN COVER. IF THE SCREW IS MISSING INSTALL ONE. When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm The Certificate of Compliance is not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. Our records show that the main drain suction outlet cover (Waterway 640-472xV) was installed 7/1/2018. The cover has a 7 year life span and must be replaced before 7/1/2025. Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. |