[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. -Observed the ORP to be 605. Have the ACC unit inspected to determine why the ORP is low.

3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Repeat Corrected During Inspection Equipment/chemical/storage areas were not secured. -Observed the lock on the spa equpiment area was not properly secured which allows the gate to be opened without unlocking it. -After the inspection, the lock was placed correctly onto the gate by the inspector, thereby correcting the violation. -ENSURE THE LOCK IS PROPERLY APPLIED, SO THE STORAGE AREA IS KEPT INACCESSIBLE TO EVERYONE BY AUTHORIZED PERSONNEL.

3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. -Observed the pH to be 7.0 -Treat the pool water so that the pH is within the acceptable range.

3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm. -Observed the alkalinity to be 30ppm. -Raise the total alkalinity to be at least 60ppm.

3701-31-04 (C)(8) / Spa water is drained at least every 30 days and is recorded
Repeat Spa water was not drained in the last 30 days. -Observed the spa has not been recorded as being drained within the last 30 days. Last date it was recorded was 8/27/23. -If the spa was drained but not recorded, record the date. If it has not been drained in the past 30 days, it is to be immediately drained.


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 23-October-2023

Comments
-NOTE THE REPEAT VIOLATIONS AND CORRECT ALL ASAP.
-MAINTAIN POOL AND WATER CHEMISTRY PROPERLY TO ENSURE THESE REPEAT VIOLATIONS DO NOT KEEP OCCURRING.