3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
The facilities were not maintained in a safe, clean & sanitary, and in good repair. The chemical storage room is dirty.
CLEAN THE CHEMICAL STORAGE ROOM. Correct By: 24-May-2021
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. Records for the last month could not be found.
All facility records must be maintained and available for review upon request.
KEEP RECORDS AVAILABLE AT THE FACILITY. Correct By: 19-May-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The weir is missing in the skimmer.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING WEIR IN THE SKIMMER. Correct By: 24-May-2021
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
Repeat Backflow prevention devices were not maintained to function properly
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
PROVIDE DOCUMENTATION OF ANNUAL BACKFLOW PREVENTER INSPECTION. Correct By: 24-May-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH Correct By: 19-May-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 17-May-2021