[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The hose bib in the pump room is not backflow protected.
Remove all cross connection hazards from the pool area. PLACE AN ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB LOCATED IN THE PUMP ROOM JUST INSIDE THE DOOR. Correct By: 01-Jul-2019
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR THE FLOW METER. KEEP FLOW RATE BELOW 196 GPM Correct By: 26-Jun-2019
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. It appears that the "NO DIVING" sings are more than 25 ft apart in 2 locations.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. PLACE ADDITIONAL 'NO DIVING' SIGNS ON THE DECK SO THEY ARE NO MORE THAN 25 FT APART. Correct By: 01-Jul-2019
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical The equipment/chemical room was unlocked.
KEEP THE PUMP ROOM CLOSED AND LOCKED WHEN THE POOL IS OPEN. Correct By: 26-Jun-2019
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. TEST AND RECORD ACC FUNCTION AT LEAST MONTHLY. Correct By: 26-Jun-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 24-June-2019

Comments
Our records show: The main drain suction outlet cover (Waterway 640-472xV) was installed 6/18/2018. The cover has a 7 year life span and must be replaced before 6/18/2025.

- Post the "DANGER: POOL CLOSED" on the gate at the end of the season and at the end of the day.
-Check reagent R-0002 to see if it has expired. Replace if it has expired.