[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present
Remove all cross connection hazards from the pool area. INSTALL AN ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB THAT IS USED TO FILL THE WADING POOL. Correct By: 06-Aug-2020
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. REPAINT THE "FT" ON THE DEPTH MARKINGS. THESE MARKINGS MUST BE AT LEAST 4 INCHES IN SIZE, WITHIN 24 INCHES OF THE EDGE OF THE WATER AND NO MORE THAN 25 FT APART. Correct By: 06-Aug-2020


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 30-July-2020