[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 27-February-2019

Comments
THE FOLLOWING WILL BE REQUIRED AT THE TIME OF MY NEXT INSPECTION
-A SIGN STATING "SWIMMING ALONE IS NOT RECOMMENDED", AND A SIGN STATING "CHILDREN MUST BE SUPERVISED"

I WAS ABLE TO LOCATE TEST RECORDS OF THE AUTOMATIC CHEMICAL CONTROLLER PRESSURE SWITCH FUNCTION, BUT NOT FOR DECEMBER OR FEBRUARY. THE TEST IS REQUIRED TO BE RECORDED AT LEAST MONTHLY.