3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not compliant covers.
Do not operate the pool without compliant outlet covers. Install compliant outlet covers prior to placing the pool back into operation.
PLUG THE SKIMMER EQUALIZER OUTLETS AT THE POOL WALL OR INSTALL VGB COMPLIANT COVERS. Correct By: 08-Jun-2022
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
CUT FILTER BACKWASH PIPE 3-4 INCHES ABOVE THE FLOOR DRAIN Correct By: 08-Jun-2022
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 68 GPM. Correct By: 08-Jun-2022
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook and/or a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool.REACH POLE WAS ONLY 10 FEET LONG
Provide the non-telescopic reach pole and personal floatation device at the pool at all times.
PROVIDE A 12 FOOT REACH POLE THAT IS NON-TELESCOPIC. Correct By: 08-Jun-2022
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
REPAIR THE EMERGENCY PHONE. Correct By: 08-Jun-2022
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use.
POST SIGN STATING "SWIMMING ALONE IS NOT RECOMMENDED". Correct By: 08-Jun-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-June-2022
Comments |
---|
Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. |