[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE THE FLOW RATE TO AT LEAST 69 GPM, BUT NOT MORE THAN 120 GPM Correct By: 15-May-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 22-August-2018

Comments
Violations that have been corrected since the inspection dated 7-27-18.
-The drain covers are secured, not loose
-an air gap is on the backwash line
-means for determining the flow rate of the waterfall pump is installed
-a first aid kit is available
-emergency numbers are posted by the emergency phone

IF THE DATE OF INSTALLATION OF THE DRAIN COVERS IS NOT KNOWN OR MORE THAN 5 YEARS, REPLACE WITH NEW DRAIN COVERS. RETAIN THE CERT OF COMPLIANCE