[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 12 hours while the pool is in use. TEST AND RECORD FREE, COMBINE AND TOTAL CHLORINE. Correct By: 03-Jun-2023
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
Backflow prevention devices were not maintained inspected within a year.
Have the backflow prevention device evaluated annually. . Correct By: 30-Jun-2023
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. TIGHTEN THE HANDRAIL TO THE STEPS.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 31-May-2023

Comments
Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room

Repair the light in the equipment room.

Our records show that the main drain suction outlet covers (Lawson MLD-FGD-1212) were installed on 5-5-19. The cover have a 10 year life span and must be replaced before 5-5-29.