3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP FOR THE FILTER BACKWASH LINE. Correct By: 04-Jul-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat the gate to the wading pool does not self-close and latch.
REPAIR THE GATE TO THE WADING POOL SO THAT IT SELF-CLOSES AND LATCHES Correct By: 04-Jul-2019
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
INCREASE pH TO AT LEAST 7.2. Correct By: 04-Jul-2019
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
DECREASE CYANURIC ACID TO LESS THAN 70 PPM. Correct By: 04-Jul-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-July-2019
Comments |
---|
Our records show: The main drain suction outlet cover (Waterway 640-472xV) was installed 7/1/2014. The cover has a 7 year life span and must be replaced before 7/1/2021. |