3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for circulation pumps. Flowmeter stuck.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 11-May-2017
Comments |
---|
Record keeping and recordings are very good. |