3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Repeat Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON THE BACKWASH DISCHARGE LINE. Correct By: 18-Jul-2017
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat The flow meter does not appear to be located properly.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
CALL BLUE WHITE TO GET INSTRUCTIONS ON HOW AND WHERE TO INSTALL THE FLOW METER. 714-893-8529. INSTALL FLOW METER PER MANUFACTURER'S INSTRUCTIONS. Correct By: 18-Jul-2017
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant. The hand rail was loose.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN THE HAND RAIL. Correct By: 18-Jul-2017
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
Repeat 12 ft. non-telescopic reach pole with shepherd's crook was not provided at the unguarded pool. The pole is only 9 ft long.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
ATTACHED THE SHEPHERD CROOK ONTO A 12 FOOT POLE Correct By: 18-Jul-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 11-July-2017