3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR OR REPLACE THE FLOW METER. Correct By: 07-Jun-2022
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY. Correct By: 31-May-2022
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The test kit provided was not in good repair. Reagents expired.
Maintain the test kit in good repair to conduct water quality tests.
OBTAIN NEW TEST KIT. Correct By: 31-May-2022
3701-31-04 (E)(3)(a) / "WARNING, NO LIFEGUARD", sign posted
The unguarded pool was in use without the "WARNING, NO LIFEGUARD" sign posted.
Post the WARNING, NO LIFEGUARD sign in a conspicuos location at all times the pool is available for use. Correct By: 07-Jun-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-May-2022
Comments |
---|
MAKE FIRST AID KIT AVAILABLE FOR USE. Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. The Certificate of Compliance for the main drain cover(s) is/are available in the equipment room. Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed on 5-30-19. The covers have a 7 year life span and must be replaced before 5-30-2026. |