3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present
Remove all cross connection hazards from the pool area.
PLACE A VACUUM BREAKER ON THE HOSE BIB IN THE EQUIPMENT ROOM.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR OR REPLACE THE FLOW METER.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow switch was not tested monthly
Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FLOW SWITCH FUNCTION MONTHLY. Correct By: 12-Jul-2023
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not supplied with Band-Aids..
Provide first aid equipment, including a first aid kit, at the pool at all times.
SUPPLY THE FIRST AID KIT WITH Band-Aids. Correct By: 12-Jul-2023
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 06-July-2023
Comments |
---|
Keep documentation of the ASSE 1013 backflow preventer’s annual inspection available at the pool facility for review by the health department. THE MAIN DRAIN COVERS WILL EXPIRE 8-1-23. WHEN INSTALLING NEW DRAIN COVERS THEY MUST HAVE A FLOW RATING HIGHER THAN THE EXISTING COVERS. DO NOT INSTALL THE SAME DRAIN COVERS. THE NEW DRAIN COVERS' FLOW RATING MUST BE AT LEAST 400 GPM. |