3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Reportedly, the drain covers have not been changed for 10 years.
REPLACE THE DRAIN COVERS. KEEP THE CERTIFICATE OF COMPLIANCE, THE CERTIFICATE OF INSTALLATION AND THE INSTALLATION INSTRUCTIONS. Correct By: 30-Sep-2018
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
TEST AND RECORD CYANURIC ACID WEEKLY. Correct By: 31-May-2018
3701-31-04 (B)(6)(b) / Replacement pipe is rigid PVC or the equivalent
Replacement pipe was not rigid PVC or equivalent. The pipe by the valve is leaking and a rubber coupling has been installed.
Replace the non rigid PVC pipe with the proper rigid PVC pipe for public swimming pools.
REMOVE THE RUBBER COUPLING AND USE ONLY RIGID PIPE. Correct By: 30-Oct-2018
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON THE DISCHARGE LINE FROM THE FILTER. Correct By: 06-Jun-2018
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not functioning for all water pumps.
REPAIR THE FLOW METER. Correct By: 06-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 30-May-2018