3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Skimmer weirs were not working or were missing.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR OR REPLACE THE WEIRS IN THE SKIMMERS. Correct By: 04-Jun-2021
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present
Remove all cross connection hazards from the pool area.
INSTALL A BACKFLOW PREVENTER ON THE HOSE BIB IN THE EQUIPMENT ROOM (THE ONE THAT IS CONNECTED TO THE WATER LINE ALSO FEEDING THE DRINKING FOUNTAIN). Correct By: 04-Jun-2021
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
VISIBLE DEPTH MARKINGS ARE MORE THAN 25 FT APART IN 4 AREAS. INSTALL 4 MORE DEPTH MARKINGS. Correct By: 04-Jun-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH Correct By: 04-Jun-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 02-June-2021
Comments |
---|
RECORD THE AAC FLOW SWITCH FUNCTION ON THE WEEKLY OPERATION SHEET. Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. The Certificate of Compliance is not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed 6/18/2018. The covers have a 7 year life span and must be replaced before 6/18/2025. |