3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Repeat Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
TEST AND RECORD ON WEEKLY LOG SHEET DAILY. Correct By: 24-Jun-2022
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
TEST AND RECORD ALK ON WEEKLY LOG SHEET WEEKLY. Correct By: 24-Jun-2022
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC FUNCTION MONTHLY. RECORD ON WEEKLY LOG SHEET. Correct By: 24-Jun-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 22-June-2022
Comments |
---|
THE POOL WAS NOT OPEN AT THE TIME OF INSPECTION. DO NOT REOPEN UNTIL FREE CHLORINE LEVEL IS 1 PPM OR MORE. Safety Data Sheets (SDS) are kept in the equipment room and Personal Protective Equipment (PPE), chemical gloves and goggles, are available for handling chemicals. The Certificate of Compliance for the main drain cover(s) is/are available in the equipment room. Our records show that the main drain suction outlet covers (Hayward WG1032 BHF) were installed 4/26/2017. The covers have a 7 year life span and must be replaced before 4/26/2024. This drain cover has a maximum flow rating of 515 gpm. When replacing the covers, ensure that the new covers' flow rating will not be exceeded. 546 gpm. The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions. A FAN SHOULD BE DIRECTED INTO THE PUMP PIT TO AVOID HAZARDOUS GAS ACCUMULATION IN A RECESSED AREA. |