[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Outlet covers were not compliant covers. Grating broken in the cover.
Do not operate the pool without compliant outlet covers. Install compliant outlet covers prior to placing the pool back into operation. THIS IS A CRITICAL OPERATING ITEM AND POSES AN IMMINENT HEALTH HAZARD. OPERATOR CLOSED THE POOL AT THE TIME OF INSPECTION. ("OPEN" FLAG TAKEN DOWN AND "WARNING POOL CLOSED" SIGN IS ON THE GATE. POOL MUST REMAIN CLOSED UNTIL MAIN DRAIN COVER IS REPLACED WITH A COMPLIANT COVER AND ALL OTHER CRITICAL ITEMS ARE CORRECTED. Correct By: 11-Aug-2022
3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Outlet covers were not installed. Equalizer lines are not plugged or covered with an approved cover.
Do not operate the pool when the outlet covers are not installed. PLUG SKIMMER EQUALIZER OUTLETS OR INSTALL VGB COMPLIANT COVERS. Correct By: 11-Aug-2022
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation. OPERATOR CLOSED THE POOL THE POOL MUST REMAIN CLOSED UNTIL THE FREE CHLORINE LEVEL IS 1 PPM OF ABOVE AND ALL CRITICAL OPERATING ITEMS ARE CORRECTED. Correct By: 11-Aug-2022
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR FLOW METER Correct By: 18-Aug-2022
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 11-August-2022