3701-31-04 (B)(6)(aa) / The Diving area/components are in good repair. No alterations have been made without plan approval
Repeat The diving board was not in good repair.
Repair the diving board or replace the diving board with one of equal length and structure.
REAPPLY THE NON-SLIP SURFACE ON THE DIVING BOARD. Correct By: 15-Jul-2021
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 635 GPM
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Repeat Deck surfaces had standing water or other hazards.
Repair areas of the deck where standing water is occurring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
REATTACH THE MISSING TILE Correct By: 13-May-2022
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage areas were not secured.
These storage areas must be kept inaccessible to everyone but authorized personnel. Secure the areas.
KEEP EQUIPMENT ROOM LOCKED Correct By: 14-Jul-2021
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
a USCG Type IV personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool. The rope is missing
Provide the non-telescopic reach pole and personal floatation device at the pool at all times.
ATTACH A 30-60 FT ROPE ONTO THE RING BUOY. ROPE MUST BE 1/4 DIAMETER Correct By: 15-Jul-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 13-July-2021