3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat Could not read flow meter and a means of determining rate-of-flow (pump curve)was not found.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-July-2016