[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The hose bib on the older building was not backflow protected.
Remove all cross connection hazards from the pool area. INSTALL AN ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB THAT IS USED TO FILL THE WADING POOL. Correct By: 01-Jul-2020
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. The "FT" markings are faint.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. REPAINT THE "FT" ON THE DEPTH MARKINGS. THESE MARKINGS MUST BE AT LEAST 4 INCHES IN SIZE. Correct By: 01-Jul-2020
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
A spot in the chain link fence has a hole in it.
REPAIR THE CHAIN LINK FENCE WHOLE. Correct By: 01-Jul-2020
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Emergency phone numbers shall be posted by the phone
POST EMERGENCY NUMBERS BY THE PHONE. "IN CASE OF EMERGENCY DIAL 911" Correct By: 01-Jul-2020


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 24-June-2020

Comments
When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm

Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals.

The Certificate of Compliance was not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review.

Our records show that the main drain suction outlet cover (Lawson MLD-FGD-1212) was installed date on 5-13-19. The cover has a 10 year life span and must be replaced before 5-13-29.

Pressure and vacuum gauges before and after the pump can be used to determine the flow rate.