3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
The disinfectant feeder pump was changed without plan approval.
SUBMIT AN ERN FORM TO THE OHIO DEPARTMENT OF HEALTH FOR REVIEW AND APPROVAL OF THE CHLORINE PUMP REPLACEMENT. Correct By: 10-Jun-2019
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH SAFETY DEVICE. THEN TEST ACC AT LEAST MONTHLY AND RECORD. Correct By: 07-Jun-2019
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh.
Obtain fresh reagents.
REPLACE THE REAGENTS FROM THE TEST KIT THAT HAVE EXPIRED. Correct By: 10-Jun-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 03-June-2019
Comments |
---|
Our records show: The main drain suction outlet cover (Waterway 640-472xV) was installed 4/1/2018. The cover has a 7 year life span and must be replaced before 4/1/2025. When repainting the pool only use white or an approved color from the list provided. Attach the fence to the stringer in the three locations noticed during the inspection. |