3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR THE FLOW SWITCH ON THE AUTOMATIC CHEMICAL CONTROLLER.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The hose bib was not backflow protected.
Remove all cross connection hazards from the pool area.
INSTALL A BACKFLOW PROTECTOR (ASSE 1011) ON THE HOSE BIB. LOCATED UNDER THE EMOTRON IN THE PUMP ROOM. Correct By: 15-Jun-2019
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. Correct By: 15-Jun-2019
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL A MEANS OF DETERMINING THE FLOW RATE ON THE WATER FALL PUMP. A VACUUM AND PRESSURE GAUGE CAN BE INSTALLED BEFORE AND AFTER THE PUMP. Correct By: 06-Jul-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate does and self-close. One gate does not latch
REPAIR BOTH GATES SO THAT THEY CLOSE ON THEIR OWN AND LATCH. Correct By: 15-Jun-2019
3701-31-04 (E)(2)(a)(iii) / A back/spine board is provided
A back/spine board without a head immobilizer and straps was not provided at the unguarded pool.
Provide the back/spine board at the pool at all times.
KEEP THE SPINE BOARD OUT ON THE DECK AREA. Correct By: 08-Jun-2019
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 07-June-2019
Comments |
---|
Equipment difficulties prohibited testing water Our records have been updated to show: The main drain suction outlet cover (New Water Solutions DS 360) was installed date on 5-30-2019. The cover has a 5 lifespan and must be replaced before 5-30-2024. Post a sign stating "WARNING:POOL CLOSED" when the pool is closed at night and closed for the season. |