3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW RATE TO 38 GPM OR LOWER, BUT AT LEAST 31 GPM Correct By: 15-Jun-2018
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention devices were not maintained to function properly
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
HAVE THE ASSE 1015 BACKFLOW PREVENTER TESTED ANNUALLY, Correct By: 28-Jun-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH FUNCTION MONTHLY. Correct By: 15-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-June-2018