3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Outlet covers were not installed on the equalizer line.
Do not operate the pool when the outlet covers are not installed.
PLUG THE EQUALIZER LINE AT THE POOL WALL. AN ENTRAPMENT HAZARD STILL EXISTS. Correct By: 30-Jun-2021
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. The flow switch was not connected.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH. Correct By: 30-Jun-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-June-2021
Comments |
---|
IT APPEARS THAT THE DISINFECTION CHEMICAL FEEDER WAS SWITCHED WITH THE pH CHEMICAL FEEDER SINCE LAST YEAR. THESE PUMPS HAVE BEEN SPECIFICALLY APPROVED FOR A SPECIFIC PURPOSE. THESE NEED TO BE SWITCHED BACK. Our records show that the main drain suction outlet covers (AquaStar WAV12/Hayward WG1032 ) were installed on 5-20-19. The covers have a 5/7 year life span and must be replaced before 5-20-24/5-20-26. The Certificate of Compliance for the main drain cover is available in the equipment room. |