3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The equalizer outlet at the pool wall is not covered with a VGB compliant cover.
PLUG THE EQUALIZER OUTLET AT THE POOL WALL OR INSTALL A VGB COMPLIANT COVER
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
TEST AND RECORD THE SVRS (STINGL SWITCH) MONTHLY. Correct By: 25-Aug-2019
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Deck surfaces had standing water or other hazards.
Repair areas of the deck where standing water is occurring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
DRY THE STANDING WATER ON THE DECK WHERE THE DEPRESSION IN THE DECK HOLDS WATER Correct By: 25-Aug-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 23-August-2019