3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The drain covers have expired.
REPLACE THE DRAIN COVERS, INSTALL COMPLIANT COVERS PER MANUFACTURER'S INSTRUCTIONS. KEEP THE CERT OF COMPLIANCE, CERT OF INSTALLATION, AND THE INSTALLATION INSTRUCTIONS. This is a critical operational item and posed an imminent health/safety hazard. THE POOL MUST IMMEDIATELY CLOSE UNTIL THE VIOLATION HAS BEEN CORRECTED AND THE HEALTH DEPARTMENT VERIFIES THE COMPLIANCE. Correct By: 29-May-2018
3701-31-04 (B)(1)(b) / SVRS device(s) shall be functional.
Critical The SVRS device that is being used as a secondary means to prevent entrapment/evisceration has not been installed at the time of the inspection.
Do not operate the pool when the SVRS is not functioning. Ensure the SVRS is operating properly prior to placing the pool back into operation.
INSTALL A SVRS. This is a critical operational item and posed an imminent health/safety hazard. THE POOL MUST CLOSE UNTIL THE VIOLATION HAS BEEN MADE AND THE HEALTH DEPARTMENT VERIFIES COMPLIANCE. Correct By: 29-May-2018
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps. The flow meter that was installed is for a 3 inch pipe. It is still installed too close to the disturbances (elbows).
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL THE CORRECT FLOW METER FOR THE PIPE AND INSTALL PER MANUFACTURER'S INSTRUCTIONS. Correct By: 04-Jun-2018
3701-31-04 (B)(6)(k) / Outlet drain covers are secure/meet ANSI/ASME A112.19.8-2007 requirements.
Critical The equalizer outlets at the pool wall pose an entrapment hazard.
COVER THE EQUALIZER OUTLET WITH A PLUG OR COMPLIANT COVER. Correct By: 04-Jun-2018
3701-31-04 (E)(2)(b)(ii) / A back/spine board with straps and head immobilizers
A back/spine board provided at the pool has peeling paint..
Paint the spine board Correct By: 04-Jun-2018
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. Correct By: 30-May-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 29-May-2018
Comments |
---|
Post a sign indicating the location of the first aid kit. |