3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT ERN FOR THE DISINFECTION UNIT REPLACEMENT.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Flow rate exceed the filter allowable flow.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE FLOW RATE TO BETWEEN 51 AND 74 GPM. Correct By: 09-Aug-2023
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gates or doors were not self-closing and self-latching.
Repair gates or doors in order to be self-closing and lockable.
MODIFY THE GATE LATCH SO IT SELF-LATCHES.
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Repeat Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
DRAIN HALF OF POOL WATER AND REFILL TO REDUCE CYA.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 07-August-2023