3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not secured. One main drain cover is missing 2 screws
Do not operate the pool when the outlet covers are not secured. Secure the covers prior to the pool being placed back into operation.
INSTALL MISSING SCREWS IN THE MAIN DRAIN COVER. Correct By: 24-Jun-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH Correct By: 24-Jun-2021
3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system
Repair or replace the disinfection system so that the pool is continuously being disinfected.
THE CHLORINE CHEMICAL FEEDER MUST BE USED. HAVE THE CHLORINE TANK FILLED AND RUN THE ACC. STOP THE USE OF HAND FEEDING. Correct By: 26-Jun-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 23-June-2021
Comments |
---|
The Certificate of Compliance for the main drain cover is available in the equipment room. Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed on 6-1-19. The covers have a 7 year life span and must be replaced before 6-1-26. |