[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week. TEST AND RECORD ALKALINITY WEEKLY. Correct By: 18-Jul-2021
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present
Remove all cross connection hazards from the pool area. INSTALL BACKFLOW PREVENTER (VACUUM BREAKER ASSE 1011) ON THE THREE HOSE BIBS. TWO IN THE EQUIPMENT ROOM AND ONE OUTSIDE THE EQUIPMENT ROOM Correct By: 18-Jul-2021
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. REPLACE THE FLOW METER. Correct By: 18-Jul-2021
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing.
Repair gates or doors in order to be self-closing and lockable. REPAIR GATE SO THAT IT SELF-CLOSES. Correct By: 18-Jul-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST pH Correct By: 18-Jul-2021
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. INCREASE ALKALINITY Correct By: 18-Jul-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 16-July-2021