3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.Skimmers are missing the weirs.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE THE MISSING WEIRS IN THE SKIMMER BOXES. Correct By: 30-Jun-2018
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The fill water line is not backflow protected. The fill spout does not have an air gap.
Remove all cross connection hazards from the pool area.
PROVIDE AN AIR GAP BETWEEN THE BOTTOM OF THE FILL SPOUT AND THE TOP OF THE FILL PIPE. Correct By: 30-Jun-2018
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The fence has gaps between the ground and the bottom rail of more than 4 inches.
REDUCE THE GAP BETWEEN THE GROUND AND THE BOTTOM RAIL ON THE FENCE TO LESS THAN 4 INCHES. Correct By: 19-Jul-2018
3701-31-04 (E)(4)(c)(i) / Lifeguards have direct line of sight of all useable areas of the pool surface and bottom
Lifeguards did not have direct line of sight of all useable areas of the pool surface and bottom.
Provide more lifeguards so that all areas of the pool surface and bottom can be within a lifeguards direct line of sight.
LIFEGUARDS MUST BE POSITIONED AT THE EDGE OF THE POOL. Correct By: 19-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 19-June-2018
Comments |
---|
USE TRI-CHLOR ONLY IN THE CHLORINATOR AS STATED ON THE UNIT. PROVIDE THE CERTIFICATE OF COMPLIANCE FOR THE MAIN DRAIN COVERS AND THE DATE OF INSTALLATION. |