3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
-Observed flow meter rate at 1.5 gpm. Minimum 23 gpm required.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 19-July-2022
Comments |
---|
Total Chlorine tested extremely high during this visit. Recommend checking equipment. Pool area was temporarily closed during this visit until repairs and or adjustments can be made. |