3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical The chlorinator is not functioning.
This is a critical operational item and poses an imminent health hazard. THE POOL MUST CLOSE UNTIL THE VIOLATION HAS BEEN CORRECTED AND THE HEALTH DEPARTMENT VERIFIES COMPLIANCE. Correct By: 01-Jun-2018
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. Correct By: 01-Jun-2018
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. The flow meter was not working.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
REPAIR THE FLOW METER. Correct By: 15-Jun-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC MONTHLY. Correct By: 15-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-June-2018