[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The skimmer equalizer outlets are not covered with an approved cover.
PLACE A VGB APPROVED COVER OVER THE SKIMMER EQUALIZER OUTLETS OR PLUG THE OUTLETS AT THE POOL WALL
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request. TEST WATER TEMPERATURE ONCE A DAY TEST TOTAL CHLORINE EVERY 12 HOURS THE POOL IS OPEN TEST ALKALINITY WEEKLY TEST THE ACC FLOW SWITCH MONTHLY
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
12 ft. non-telescopic reach pole with Shepherd's crook
Provide the non-telescopic reach pole WITH A SHEPHERD'S CROOK..


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 16-July-2019

Comments
Corrections made since the 7-1-19 inspection
-the spine board is in pool area easily available and visible
-the skimmer weirs are in place
-an air gap is on the filter discharge pipe