3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Repeat Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT AN ERN TO ODH FOR THE PUMP REPLACEMENT. Correct By: 13-Mar-2023
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 2 ppm for the spa
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 2 ppm or above prior to placing the spa back into operation.
THIS VIOLATION IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. CLOSE SPA UNTIL THE SPA FREE CHLORINE LEVEL IS ADJUST ED TO AT LEAST 2 PPM. CALL ME WHEN CORRECTED. THE OPERATOR WAS CALLED TO NOTIFY OF VIOLATION AND TO CLOSE. Correct By: 06-Mar-2023
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat SVRS test results were not maintained.
The test results/service records for these devices must be kept on site for review.
TEST AND RECORD ON THE LOG SHEET THE SVRS.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY Correct By: 08-Mar-2023
Facility Type: Spa
[?] Inspection Type: Follow-up
Inspection Date: 09-March-2023