3701-31-04 (B)(6)(a) / Pool structure is water tight
Tiles were missing and upper sealant / caulking was missing on the south side of the pool.
Repair missing / loose tiles and add caulking to provide water tight pool.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. Flow was reading 160, required to be 175 -200.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 25-July-2017