3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The light in the pump room does not work.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE LIGHT IN THE PUMP ROOM. Correct By: 21-Jul-2017
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The fill line does not have backflow protection
Remove all cross connection hazards from the pool area.
INSTALL AN ASSE 1013 BACK FLOW PREVENTER ON THE INCOMING WATER LINE INTO THE PUMP ROOM. Correct By: 04-Aug-2017
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. Depth markings and "No diving" signs are faded and in some locations more than 25 ft apart.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
RE-MARK THE DEPTH MARKINGS AND "NO DIVING" SIGN SO THAT THEY ARE CLEARLY MARKED AND NO MORE THAN 25 FT APART. Correct By: 21-Jul-2017
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat The gate is damaged and does not self close.
REPAIR THE GATE SO THAT IT SELF CLOSES. Correct By: 04-Aug-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-July-2017
Comments |
---|
I FORGOT TO LOOK AT THE RECORD SHEET FOR TESTING OF CYANURIC ACID WEEKLY. CYANURIC ACID MUST BE CHECKED WEEKLY AND PH AND CHLORINE CHECKED EVERY 4 HRS. I FORGOT TO CHECK THE TEST KIT FOR FRESH REAGENTS. REAGENTS MUST BE FRESH YEARLY. ENSURE THAT THE SPINE BOARD IS PUT OUT WHEN THE POOL IS OPEN. THE POOL WAS CLOSED AT THE TIME OF INSPECTION. MARK THE MAX AND MIN FLOW RATE BY THE FLOW METER OR THE THROTTLE VALVE. MAX IS 282 GPM AND THE MIN IS 106 GPM. |