3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Grains of sand are inside the flow meter and the indicator is stuck.
All equipment must be maintained in accordance with the manufacturers specifications.
CLEAN THE FLOW METER TO FREE THE INDICATOR FLOAT. Correct By: 09-Aug-2017
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. The "11" depth markings are missing "ft" markings. The "NO DIVING" markings are more than 25 ft apart.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
PROVIDE ADDITIONAL "NO DIVING" SIGNS SO THEY ARE NO MORE THAN 25 FT APART. PROVIDE THE "FT" MARKINGS BESIDE THE "11". Correct By: 01-Apr-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 08-August-2017