3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The automatic chemical controller was not functioning properly. Reportedly, a call has already been made requesting repairs.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR ACC. Correct By: 01-Mar-2019
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FLOW SWITCH MONTHLY. Correct By: 27-Feb-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 27-February-2019
Comments |
---|
Corrections that have been made since the last inspection dated 10-31-18. -a weir is in the skimmer -chlorine level is 2.4 acceptable -water tests have been done and recorded (except for the ACC flow switch function) |