[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (A) / All construction or alterations of a public swimming pool are approved
Repeat The Ohio Department of Health has not notified the LCPH that they received an Equipment Replacement Notification for the replacement of the pump
ENSURE THAT THE EQUIPMENT REPLACEMENT NOTIFICATION FOR THE PUMP HAS BEEN SENT TO THE OHIO DEPARTMENT OF HEALTH.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The flow meter is not working.
All equipment must be maintained in accordance with the manufacturers specifications. REPAIR THE FLOWMETER
3701-31-04 (B)(6)(c)(v) / Discharge of water from a public swimming pool shall be in accordance with OEPA.
Water from the pool was not being discharged to a sanitary sewage system.
Provide documentation that the method of water discharge is approved by the OEPA. I WILL CHECK ON THE REQUIREMENTS FOR CONNECTIONS TO THE SANITARY SEWER
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. ADD "NO DIVING" AND DEPTH MARKINGS SO THEY ARE NO MORE THAT 25 FT APART AND THAT ARE NOT MORE THAN 24 INCHES FROM THE POOL SURFACE.
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
Repeat The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Swimming Alone is Not Recommended" signs at all times the pool is available for use.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 30-July-2018

Comments
The drain cover appears to be a Paramount SDX 159-2212. Please keep a copy of the certificate of compliance