3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Weir broken in skimmer.
All equipment must be maintained in accordance with the manufacturers specifications.
REPLACE BROKEN WEIR IN SKIMMER. ENSURE WEIRS FLOAT FREELY WITH THE WATER LEVEL WHEN INSTALLED.
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 21-October-2021
Comments |
---|
Since the pool is used primarily as a therapy pool and the pool is located at a medical facility, the local health department decided that the water temperature can exceed 90 degrees, if no health or safety hazards exist and no strenuous activity takes place in the pool. This decision is subject to review and change. If the pool is used exclusively as a therapy pool, no license is required from the local health department. |