3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
KEEP SPA CLOSED UNTIL ACC IS FUNCTIONING PROPERLY. OPERATOR PLACED SPA CLOSED SIGN ON CHAIR IN FRONT OF SPA AT THE TIME OF INSPECTION. CALL 440-219-7158 WHEN REPAIRED AND BEFORE REOPENING. Correct By: 31-Aug-2022
3701-31-04 (B)(1)(l) / Electrical hazards shall not exist.
Critical Electrical hazards were present in the pool area. Light fixture in the spa not secure.
Do not operate the pool when an electrical hazard is present.
REPAIR LIGHT FIXTURE IN THE SPA TO PREVENT ELECTRICAL HAZARD. Correct By: 31-Aug-2022
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
TEST AND RECORD ALKALINITY WEEKLY, WATER TEMPERATURE DAILY, WHEN SPA IS DRAINED, AND THE ACC FUNCTION TEST RESULTS MONTHLY. RECORD ON THE WEEKLY LOG SHEET. Correct By: 02-Sep-2022
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage areas had hazards present. Chlorine leaking from chemical feed pump tubing.
These storage areas must be kept free of hazards to avoid a serious public health nuisance.
REPAIR CHEMICAL FEED TUBING LEAK IN BOTH LOCATIONS. Correct By: 31-Aug-2022
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents. Chemical storage room has rugs, empty chemical container open and tipped over.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
CLEAN CHEMICAL STORAGE ROOM. REMOVE RAGS AND EMPTY CONTAINER. Correct By: 02-Sep-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 02-Sep-2022
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 31-August-2022
Comments |
---|
CALL WHEN REOPENING THE SPA 440-219-7158 |