[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Repeat Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week. TEST AND RECORD ON THE WEEKLY SHEETS THE CYANURIC ACID WEEKLY. Correct By: 09-Aug-2017
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. REPAIR THE LIGHT IN THE FILTER ROOM. Correct By: 01-Apr-2018
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present
Remove all cross connection hazards from the pool area. INSTALL AN ASSE 1013 BACKFLOW PREVENTER ON THE WATER LINE COMING INTO THE FILTER ROOM Correct By: 01-Apr-2018
3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Repeat Throttle valve was not properly maintained/adjusted.
Throttle valves must be maintained in the same position was when originally installed and approved. Restore the setting of the throttle valve and lock it into place. TAG THE THROTTLE VALVE WITH THE MAXIMUM AND MINIMUM FLOW. MAX 282 GPM, MIN 106 GPM. Correct By: 09-Aug-2017
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. RE-MARK THE "NO DIVING" SIGNS AND DEPTH MARKINGS. THEY MUST BE NO MORE THAN 25 FT APART. Correct By: 01-Apr-2018
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Perimeter barrier had gaps greater than 4 inches.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier. REPAIR THE GATE SO THAT IT SELF-CLOSES. Correct By: 01-Apr-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST PH. Correct By: 09-Aug-2017
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Repeat The reagents are more than 1 year old.
REPLACE REAGENTS AT LEAST YEARLY. Correct By: 01-Apr-2018
3701-31-04 (E)(2)(a)(iii) / A back/spine board is provided
Repeat A back/spine board without a head immobilizer and straps was not provided at the unguarded pool.
Provide the back/spine board at the pool at all times. KEEP THE SPINE BOARD OUT AVAILABLE AND IN VIEW FROM THE DECK. Correct By: 09-Aug-2017


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 08-August-2017