3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention devices were not maintained to function properly
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
-No recent backflow inspection noted. Backflow prevention devices shall be inspected yearly. Documentation shall be available upon request.
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Repeat Pool chemical storage at pool side is unsecure.
Repair or replace lock securing accesse to pool side chemical storage.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
-pH tested at 7.0 ppm at time of inspection
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
-Total alkalinity was tested at 30 ppm at time of inspection.
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly.
Obtain fresh reagents and store them properly
-Observed expired reagents in test kit.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 19-January-2023