3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
-Observed the flow rate exceeded the maximum flow rate for the filter.
-To achieve a proper turnover rate and filtration, adjust the flow rate to ensure that it is between 314-566 gpm.
All equipment must be maintained in accordance with the manufacturers specifications.
3701-31-04 (B)(6)(n) / Proper pool operating water level is maintained
The operating water level of the pool was not maintained.
-Observed the water level was too high, so the water level was quite a bit above the gutters, so the gutters were not properly skimming the top of the pool.
-Adjust the water level in the pool to ensure the gutters can function properly.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 03-August-2023
Comments |
---|
-If the chlorine is less than 1 ppm, the pool is to be closed, and the water is to be retested and achieve at least 1 ppm prior to reopening. This should be documented in the records. |