[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical Chemical controller is overfeeding chlorine so the level is excessive in the 10parts per million range. This has been a continuing problem and needs to be resolved.
Have the system checked/serviced to assure it is working properly. Correct By: 01-Jul-2015
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was 6.8, outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 10-June-2015