3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH). The erosion feeder is being replaced with a chemical feeder pump.
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN ERN TO ODH FOR THE REPLACEMENT OF THE CHEMICAL FEEDER. THE PENTAIR RAINBOW EROSION FEEDER IS BEING REPLACED WITH AN AUTOMATIC CHEMICAL CONTROLLER HAYWARD HC2000. Correct By: 30-Jul-2020
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE LEAKING CHEMICAL FEEDER TUBING AND ANY OTHER LEEK IN THE CIRCULATION SYSTEM. Correct By: 30-Jul-2020
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gates did not self-close.
REPAIR THE WEST SIDE AND SOUTH SIDE GATES SO THEY SELF-CLOSE AND SELF-LATCH. Correct By: 30-Jul-2020
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical The equipment room was not locked.
KEEP THE EQUIPMENT ROOM LOCKED. Correct By: 24-Jul-2020
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored on the floor and acid stored over the chlorine in the equipment room
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
STORE THE BAGS OF CHEMICALS OFF OF THE FLOOR. DO NOT STORE DIFFERENT CHEMICALS OVER EACH OTHER. Correct By: 30-Jul-2020
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical container for the chlorine pucks is going to be used for acid storage.
Properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
DO NOT USE OR REUSE A CONTAINER FOR ONE CHEMICAL THAT WAS USED FOR A DIFFERENT CHEMICAL. DO NOT REUSE THE CHLORINE BUCKET FOR THE MURIATIC ACID. Correct By: 24-Jul-2020
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
LABEL THE CHEMICAL TANKS. Correct By: 30-Jul-2020
3701-31-04 (D)(02) / Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
Critical The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system
Repair or replace the disinfection system so that the pool is continuously being disinfected.
OBTAIN AND USE TRI-CHLOR FOR THE EROSION FEEDER. DO NOT CONTINUE TO HAND FEED THE CHLORINE. DO NOT USE THE AUTO CHEM CONTROLLER UNTIL THE ACC IS APPROVED BY THE OHIO DEPARTMENT OF HEALTH. Correct By: 24-Jul-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 24-July-2020
Comments |
---|
Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. The Certificate of Compliance was not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. The main drain suction outlet cover (AVSCO A+A Manu AVSC 8x32 ) was installed 6-3-20. The cover has a 7 year life span and must be replaced before 6-3-27. |